A methanol hydrogen generator set factory should combine liquid-circuit tightness testing, gas-side pressure-hold testing, sensitive leak localization, valve-seat checks, and verification during operation. Each test answers a different question. A pressure gauge can reveal a loss from an isolated section, but it cannot identify the leaking joint or prove that a closed fuel valve seals internally.
The test plan must follow the actual fuel arrangement. A methanol reformer feeding a fuel cell differs from a system supplying hydrogen-rich gas to an engine. Map the liquid feed, reformer, gas conditioning equipment, fuel delivery piping, and purge connections before choosing test boundaries. Include every installed component that can release fuel or allow it into an unintended space.
Use the piping drawing to divide the system into sections with compatible pressure ratings. Tanks, pumps, reformers, filters, regulators, and downstream fuel equipment may have different limits. Isolate components that cannot withstand a section’s test pressure, and document how those components and their final connections will be checked separately.
Pressure-strength testing and leak testing serve different purposes. A strength test assesses the pressure boundary’s structural integrity under a prescribed procedure. A tightness test measures or detects leakage under defined conditions. Passing either one does not automatically satisfy the other. Avoid applying a generic pressure multiplier across the complete assembled fuel system.
The applicable pressure-equipment, fuel-gas, electrical, and installation requirements depend on the equipment configuration and destination. Translate those requirements, component limits, and design risk assessment into a written procedure covering:
“No leakage” needs a measurement definition. No visible liquid, no growing bubbles, and no instrument response above a specified threshold are different acceptance statements. A detector’s sensitivity must be adequate for the permitted leak rate.
Start with assembly inspection: material compatibility, seal selection, hose routing, fitting assembly, weld condition, supports, and access to joints. Methanol compatibility applies to elastomers, sealants, and test fluids as well as metal parts. A sound-looking connection can still contain an unsuitable seal that deteriorates after fuel exposure.
Conduct any required strength test using the engineering-approved procedure. Liquid testing generally stores less energy than pneumatic testing, but the test liquid must suit the equipment. Water can create contamination, corrosion, or drying problems in some reformer and fuel-processing assemblies. Any temporary blanks, isolated components, or disconnected lines must be tracked through restoration.
For production tightness testing, a compatible nonflammable medium can help identify assembly leaks before methanol charging. Dry nitrogen pressure testing may suit some sections, provided the pneumatic hazards, pressure limits, ventilation, and oxygen-displacement risk are controlled. Keep the pressure source isolated during measurement; a connected regulator can replenish losses and hide a leak.
Follow with a controlled liquid check where required by the release procedure. Examine pump seals, filter bowls, drains, level connections, flexible lines, and dosing connections under the intended operating conditions. Use suitable containment and inspection methods; smell is not an acceptance tool. Static testing alone may miss a pump seal that leaks only while rotating.
If any section operates under suction, assess inward leakage too. A joint that remains dry during a positive-pressure check can still admit air during operation. Use a qualified vacuum or operational test appropriate to that section.
A gas pressure-hold test is useful for screening an isolated assembly, but temperature changes can overwhelm the pressure signal from a small leak. Gas cools after filling, while surrounding equipment may warm during the test. Flexible hoses can also expand and cause an initial pressure decrease.
Allow stabilization before recording the starting pressure. Record gas temperature where practical, account for atmospheric pressure when interpreting gauge readings, and choose instruments suited to the expected change. The test volume matters: the same leak produces a smaller pressure drop in a larger volume. A hold time suitable for a short pipe cannot automatically qualify a complete fuel train.
Local detection then identifies the source and provides sensitivity that a pressure gauge may lack. Select the method according to the assembly:
Do not substitute one test gas for another without qualifying the method. Gas properties, pressure, seal behavior, and instrument response affect the result. A helium measurement requires an engineering basis before it can be interpreted as an allowable hydrogen leak rate.
Hydrogen-rich reformate can also contain carbon monoxide and other gases. Detection must address the actual stream’s hazards; a combustible-gas reading alone does not establish that toxic exposure is controlled.
External tightness checks do not show whether fuel passes through a closed shutoff valve. Test safety isolation valves across their seats using the specified pressure direction and differential. Measure downstream leakage through an approved flow, pressure-rise, or equivalent method, with downstream volume and temperature controlled.
Where two shutoff valves and an intermediate vent are fitted, verify each valve and the vent path separately. A whole-train pressure test can conceal one leaking seat behind another valve that seals correctly.
Regulators, check valves, purge valves, and bypasses also need checks appropriate to their function. For reformers and heat exchangers, assess potential leakage between process passages where the design creates that risk. An external sniffer test cannot establish that fuel remains separated from a neighboring water, air, or heating circuit.
Component certificates support incoming inspection, but final assembly introduces additional joints, mechanical loads, and connections. Repeat the relevant tightness checks after installation in the enclosure and after any repair that opens the fuel boundary.
Container layout affects inspection access and gas movement. AMICO’s 1200kW Silent type Containerized Gas Generator Set, model AMC1200NS, illustrates the enclosure and automatic-control considerations of a packaged gas genset. Methanol or hydrogen service requires its own fuel-system design qualification; power rating and container format do not establish fuel compatibility.
During controlled commissioning, inspect through startup, stable operation, shutdown, and cooldown. Thermal expansion can disturb seals, while engine vibration can load unsupported piping. Include a repeat cold check when required, because a connection may behave differently after a thermal cycle.
Verify the protective functions alongside these inspections. Check detector response using a suitable test gas, ventilation interlocks, alarm outputs, automatic fuel isolation, and restart permissives. Software signal simulation checks control logic but does not prove that a physical sensor detects gas. Conversely, successful detector testing does not prove fuel-system tightness.
Record the unit serial number, drawing revision, tested boundaries, valve positions, medium, pressure, temperature, stabilization period, duration, results, and instrument identification. For tracer testing, include concentration and calibration-check results. Identify exclusions and retain evidence that final connections were tested after temporary equipment was removed.
A failed result should lead to isolation, repair, and retesting of the affected section. Recheck neighboring connections disturbed during the repair. Extending a test until the reading appears stable does not resolve an unexplained loss.
Release the genset when every fuel boundary has traceable acceptance evidence, internal shutoff leakage meets its separate limit, and operation has introduced no unresolved leaks. The most useful starting document is a marked piping drawing showing exactly how each boundary will be tested and what constitutes a pass.